FDF-MG Solenoid valve

Model:
Price:0US$

General

FDF-MG is specially designed for R410A system,it can be also used for liquid,suction,discharge gas and refrigerant service.
 Details

Characteristics

          FDF~MG is servo pilot operated solenoid valve for liquid, suction and hot gas application.
          Full range of solenoid valves for refrigeration and air condition application.
          Wide choice of coils for AC and DC.
          Suitable for R410A refrigerants、HFC & HCFC.
          Media temperature -40℃~+105℃, Max media temperature during defrosting +130℃.
          Environmental temperature -40℃~+55℃.
          Max working pressure 45 bar.
          Maximum test pressure (liquid line) ≥68 bar.
          Versions with UL and CUL approval can be supplied to order.

Technical date
Nominal Liguid Capacity(k)w
 
Model
Liguid
Suction
Steam
R22
R134a
R404A
R507
R407c
R410A
R22
R134a
R404A
R507
R407c
R410A
R22
R134A
R404A
R507
R407c
R410A
FDF3G
6.2
3.9
3.7
5.7
6.48
0.675
0.54
0.40
0.62
0.702
2.92
2.32
1.73
2.66
3.02
FDF6MG
18.4
14.7
11.0
16.8
19.2
2.0
1.6
1.2
1.84
2.08
8.64
6.88
5.12
7.89
8.96
FDF8MG
23.0
18.4
13.8
21.0
24.0
2.5
2.0
1.5
2.3
2.6
1.8
8.6
6.4
9.87
11.2
FDF10MG
43.7
35.0
26.2
39.9
45.6
4.8
3.85
2.88
3.99
5.02
20.54
16.45
12.15
18.63
21.3
FDF15MG
69.0
55.2
41.4
63.0
72.0
7.59
6.07
4.55
6.93
7.92
32.24
25.8
19.35
29.42
33.65
FDF20MG
103.5
82.8
62.1
94.5
108
11.38
9.10
6.83
10.39
11.88
48.37
38.7
29.02
44.17
50.48
                                                  
Rated liquid and suction vapour capacity is based on evaporating temperature te=4.4℃,liquid temperature ahead of valve t1=38℃,and pressure drop in valve R134a △P=0.15 bar, R22、R404A、R507、R407c、R410A  ΔP=0.21bar.
Rated hot gas capacity is based on condensing temperature tc=+40℃,pressure drop across valveΔP=0.8bar,hot gas temperature th=+65℃,and subcooling of refrigerant Δtsub=4K.

Installation

The valve should be installed in horizontal pipe line under vertical position. The flow direction must be in the arrow direction.
The supply voltage must meet the rated input voltage shown on the label of the coil. Coil taking away from valve when energized in coil is forbidden.
When brazing the valve with connect tube in system,follow points are very important.
Before brazing, coil must be taken away and with wet rags covering the valve body to avoid damage.
The brazing flame must be avoided facing the valve body.
 It is better to use low temperature type silver to braze.
For the valve with hand lever,you must turn the lever firstly,then make leakage test to protect diaphvagm.


 